QUEENSLAND
DEPARTMENT OF PUBLIC WORKS AND HOUSING
BUILT ENVIRONMENT RESEARCH UNIT
EARTHQUAKE DAMAGE MITIGATION
GUIDELINES
SEPTEMBER 1997
HUGHES CONSULTING SERVICES PTY LTD
Floor 1, 31 Station Road
P.O.Box 276
INDOOROOPILLY QLD 4068
Telephone 07 3378 9111
Facsimile 07 3878 1252
EARTHQUAKE DAMAGE MITIGATION GUIDELINES

BENCHMARK
It is intended that these EARTHQUAKE DAMAGE MITIGATION GUIDELINES be used by relevant Queensland Government departments, agencies and others in the determination of the life cycle of buildings and other structures from their inception to disposal, and which will incorporate the PLANNING, PROCUREMENT, ASSET MANAGEMENT, MAINTENANCE and DISPOSAL aspects of such developments.
These guidelines have been prepared with the assistance of Hughes Consulting Services Pty Ltd, Project Managers and Consulting Engineers .
APPENDIX A - FLOW CHARTS
A4 ASSESSMENT OF EXISTING BUILDINGS
APPENDIX B - CHECK LISTS
B1 PLANNING
B2 PROCUREMENT
B4 MAINTENANCE
APPENDIX C - LOCALITY CHART, DIAGRAMS AND PHOTOGRAPHS
C3 AREAS of CONCERN in STRUCTURAL SYSTEMS with IRREGULAR CONFIGURATIONS
C4 PHOTOGRAPHS
The aim of these Guidelines is to ensure that any building or structure for which the Queensland State Government is responsible shall have adequate consideration made of requirements and protection should an earthquake occur, in addition to the requirements covered by the relevant current Building Codes and Australian Standards.
These guidelines should be set also to provide an assessment to maximise protection for the building's users and human life generally in case of earthquake occurrence.
Both existing and new buildings shall be managed in a manner that minimises risk of damage in accordance with methods and strategies recommended by earthquake design mitigation specialists.
NOTE:
While these Guidelines provide a generalised earthquake mitigation assessment guide, they do not cover all cases and types of buildings that may be identified. In those cases, reference should be made to a qualified experienced specialist practitioner.
The objectives for the provision of these Guidelines are:
Earthquakes are caused by the differential movement of the tectonic plates which form the earth's crust. The differential movement of the plates, both at the plate's boundaries and within a plate, generate energy which is stored until that energy is greater than can be resisted by the matrix of rock which forms the earth's crust. The "explosion", upon release of this energy, generates a series of compression waves which pass through the crustal strata at varying speeds and magnitude depending on the properties of the strata encountered.
The waves so formed are a complex mixture of horizontal and vertical oscillations known as P, S and L waves. It is the S waves that generally cause the damage to buildings, services and other infrastructure. The waves cause a peak ground acceleration or motion of the ground in horizontal, vertical and lateral directions. It is this motion of the underlying ground that the structure and its foundations have to be able to resist
Figure 3.1-Typical Seismograph Output

The soil type and profile on which the building is situated directly effects the size of ground motion that will be encountered. For instance, the ground motion in a soft silty sand can generally be more damaging than the ground motion from the same earthquake intensity in a dense gravelly soil. However damage can also be associated with the presence of faults in rock formations, lineaments and at the interface in major geological features. Large lateral movements can often occur at these faults following earthquakes.
Australia is located within the central section of the Australian tectonic plate. Hence all of the earthquakes that have been experienced directly within Australia are intraplate earthquakes. These types of earthquakes are limited to about the top 50 kilometres of the earths crust, are random in their location, and are generally smaller in magnitude, whereas intraplate earthquakes that are associated with tectonic plate movements may be reasonably determined in there location and magnitude. Northern Australia, especially in Northern Territory and northern Western Australia can experience the effects of intraplate earthquakes which occur in Indonesia or under the seas between Australia and Indonesia, at the tectonic plate margin or boundary.
The hazard of a particular area is determined from past events whether by electronic data or by peoples' recollections of vibrations and movement felt.
Queensland's hazard areas are generally located within a 200km strip west from the coast or off the coast to the continental shelf.
The Maryborough - Gladstone region due to the intensity and number of earthquake occurrences is considered to have a medium hazard rating, with the remainder of the coastal area medium to low. Specific pockets where earthquakes have occurred have higher hazard ratings while western areas due to the lack of earthquake records are considered as having a low hazard rating.
Only since 1993 for the whole of Australia, and previously since 1979 for specific locations in Australia, has earthquake loading for specific building types had to be considered. Hence there is a need, due to the current litigious nature of the world (e.g. following the failure of the Newcastle Workers' Club caused by the 1989 Newcastle Earthquake), that certain planning, design, maintenance and operation building procedures have to be considered. The Foreword to "Australian Standard AS1170 Part - 4 - 1993, Earthquake Loads" states:
"The purpose of designing structures for earthquake loads is to -
(a) minimize the risk of loss of life from structure collapse or damage in the event of an earthquake:
(b) improve the expected performance of structures; and
(c) improve the capability of structures that are essential to post-earthquake recovery to function during and after an earthquake, and to minimize the risk of damage to hazardous facilities.
The design of structures to this Standard does not necessarily prevent structural and non-structural damage in the event of an earthquake. The provisions provide the minimum criteria considered to be prudent for the protection of life by minimizing the likelihood of collapse of the structures.
The ground motions specified in this Standard are for the 'design earthquake' based on an estimated 90% probability of these ground motions not being exceeded in a 50-year period.
The detailing requirements specified in this Standard are of a general nature related specifically to earthquake resistant design. Specific detailing appropriate for each material (concrete, steel, masonry, timber, etc) will be found in the relevant material Standards."
and is the basis for assessment of all buildings and structures for earthquakes in Australia.
These Guidelines are based on the above stated premise.
In the event of an earthquake occurring and assuming that the building has been designed to resist earthquake loads, minor damage to non-structural and structural elements may occur.
Building elements likely to be damaged in a conforming building during an earthquake are:-
Any damage to these types of items may not render the building unusable, nor may it lose its functionality. Should the building remain "operational", although "damaged" then this means that the frame has provided the required structural resistance.
If a building is considered critical for post-disaster functions, and the building frame remains intact but the essential services which are relied upon to ensure post-disaster functionality fail, then the building has "failed" to meet the requirements of the design. For example, if a building that requires water supply, backup power, lighting, etc., for post-disaster functions fails to provide these services due to the failure of, say, one of these systems, then the building has "failed".
AS1170 Part 4-1993 Earthquake Loads recognises as indicated previously, that some minor damage may occur during an earthquake. To design a building to sustain NO damage during a probable maximum sized earthquake, is considered uneconomical. Hence it is essential that the damage that will occur is minimised and sustainable but NOT catastrophic.
The most common building element damages caused by an earthquake, are:-
And many more.
If you are unsure - ASK!!
The main issues to be covered by these Guidelines are related to the potential damage to the various buildings and services that have to be considered for earthquake loading. This has to be considered during the planning, design, procurement, asset management and disposal phases of the life of a building, in relation to:
The following issues are not covered by these Guidelines:-
Should more information be required or specific answers to any of the above exclusions to these guidelines be required, these can be obtained from consultants experienced in the practical design for earthquakes or the provision of emergency services.
If you are unsure - ASK!!
The following definitions are provided to assist the user of the guidelines.
Gravitational Acceleration g
Acceleration due to gravity taken as 9.81 m/s2.
An irregular structure is defined as a building that in plan or elevation varies in width from one section of the building to another by more than 15%. Typically this would be an "L" or "U" shaped building or large area podium floor plan with a slender tower over.
A "soft storey" is a section of the building that varies in stiffness by more than 30% to the floor above or below. These are typically open areas, under cover carparks, or with a large open foyer or vestibule, with a rigid framed building over.
The following soil profiles are defined in AS1170 Part 4- 1993 and are used to determine forces on the foundations of structures. Each of the soil types has been given a type letter to enable easier use within these guidelines.
1 General structures Type A Low strength rock or better; Type B (i) Extremely low strength rock or better; (ii) Not more than 30m of medium dense coarse sand and gravel, firm or stiff clays or controlled fill; Type C More than 30m of medium dense coarse sand and gravel, firm or stiff clays or controlled fill; Type D A soil profile of 20m or more with 6m to 12m of very soft to soft clays, very loose to loose sands, silt and/or uncontrolled fill. Type E More than 12m of very soft to soft clay, very loose to loose sands, silt and/or uncontrolled fill. 2. Domestic Structures Normal Other than Soft Soft Any soil profile with more than 5m of soft clay, loose sand, silt and/or uncontrolled fill.
Comparative Risk Factor
The "Comparative Risk Factor" has been developed for these Guidelines to assist planners, designers, etc, in the selection of the most suitable site for a building. The factor is subjective and dependant on the type or component of the building or structure being assessed.
The user should also refer to the following references (latest editions) for full definitions and explanations of terms explanations, and definitions,, to fully explain those defined above:-
Damage
There were four (4) levels of damage to buildings used after the Newcastle earthquake. Notices to this effect were placed on buildings and colour coded accordingly.
Damage can be defined as either minor or major, with subdefinitions of each.
Minor
TYPE A Little or no damage, building is satisfactory for continued habitation.
eg. hairline cracks visible.
TYPE B Some damage. Building is satisfactory for continued habitation but repairs are required
Major
TYPE C Sufficient damage to building to be hazardous to occupants although building is repairable.
TYPE D Building is hazardous to public and cannot be repair to original condition. Building is to be demolished.
It is assumed that the user of these Guidelines is fully familiar with building terms, construction, operation and maintenance procedures and terms and/or design methods in the relevant fields of expertise of the building or building services industry generally.
Should any user of these Guidelines not have the required understanding, expertise or experience in the use of these terms, then professional assistance must be sought to understand or interpret these Guidelines.
Many publications are available on the matter of earthquakes. Material used in the preparation of these guidelines is listed in 16.0 Bibliograghy. Internet sites that may be of use to the reader are also listed in the bibliography.
If the user is in doubt regarding anything in these Guidelines - ASK!!
Buildings and services have to be planned, designed, constructed and maintained to ensure that in cases of earthquake occurrence, that an environmental management plan is established. In such cases, all damage should be confined to ensure that such damage does not increase injury or death to users of the building and services and to minimise potential pollution and further injury from damaged services e.g. sewerage, live electric wires, etc.
The need to maintain water supply, electricity and other services to control fire outbreaks, provide air-conditioning and other facilities for post-disaster facilities and refrigeration for the maintenance of food supplies, are all aspects of a management plan to ensure the sustaining of environmental equilibrium after an earthquake occurrence.
The need for an environmental management plan for all activities is essential and is the responsibility of the directors and managers of the operation of a building or service.
10.2 Environmental Performance
It is recognised that the provision of retrofitting or upgrading a structure to resist earthquake loads may cost more than the previously designed non-earthquake resistant structure. It is also recognised that the repair of damaged buildings, loss of life and extra resources required to reinstate buildings and services can in fact cost more in the long term than the original construction . This all adds to the life cycle cost and in turn the environment upon which it can impact. Hence while some extra resources may be required initially, long term, if earthquake disaster occurs, the benefits should be reaped.
Retro-fitting of buildings to suit current design standards especially for buildings designed for large occupancy, institutional or post-disaster uses, may cost more than to provide a totally new building designed and constructed specifically to meet the new requirements.
11.1 Assessment of Existing Buildings
It is important to determine or identify which or what section of any existing building will be susceptible to earthquake damage due to their construction and/or building components. This will allow for a management plan to be developed for the building and the use, if appropriate, of the building to be modified if required so as to minimise potential injury or loss of life. It also allows modifications to the building to reflect new design requirements and minimise any potential hazard. Typically, this would involve the recording of the framing system, facade system and also whether the building contains any vulnerable elements, such as unreinforced masonry, soft storeys, irregular structure shapes and any mechanical and electrical systems that may be required for post-disaster functionality of the building.
The following flow chart gives the procedure that should be taken to assess the vulnerability of an existing building.
click here to see flow diagram for procedure to assess an existing building
There are numerous items that have to be considered in the design of a new building. Those professions involved in the design must ensure that the functionality of a building continues after an earthquake. This is most important, especially if the building has a post-disaster function.
click here to see flow diagram for procedure in planning for new building
Planning involves the selection of the appropriate facade systems, structural framing and foundation system, anchorage of mechanical and electrical components and provision for sufficient flexibility between, and in structural and moveable items. Also necessary, is the ability for occupants to exit the building quickly in an emergency such as an earthquake and also the ability for emergency service personnel to enter the building after such an occurrence.
All buildings will "move" to some extent during an earthquake and some may suffer a permanent "set," which could jamb doors and windows, crack walls or identify differential settlement of foundations, etc.
If a building is designed to meet the requirements of the AS1170 Part4-1993, there should be in Australia, good to adequate performance of the building during and following an earthquake event. However if the building is not designed in accordance with the above Standard, then the level of vulnerability and non performance can be high to extremely high.
click here to see flow diagram for procedure in designing new buildings
11.3 Management of Existing Buildings
A post-disaster management plan and building operational plan should be developed for each building to enable that building to continue to function after an earthquake. The building management plan has to be developed for the life of the building as a part of its operational and emergency management plan.
Critical to any post-disaster function and performance of a building,, the minimisation of loss of life and injury is the development of evacuation strategies and plans. This may include an inventory of equipment associated with the building that could be used in a post-disaster emergency response. eg a tractor that could clear rubble to provide access to emergency service personnel and provides for occupants to exit. Emergency Schedules and Procedures for checking the structure for weakened or damaged components, e.g. brick ties or cracks in brickwork and masonry, missing anchorage bolts for service equipment, etc, should be developed for each building.
The following flow chart outlines the procedures that should be undertaken to prepare these management and disaster strategies .
click here to see flow diagram for procedure to manage existing buildings
The strategic plan would include the development of procedures for the following:
The provision of the above plan provides help to identify changes in use and elements that could alter the vulnerability of the building in the event of an earthquake.
11.4 Maintenance of Existing Buildings
A maintenance plan should be developed to ensure that the building continues to function in accordance with the management strategy that has been developed for the building.
The following flow chart indicates the processes that are required to be undertaken to achieve this maintenance program and some of the items that need to be considered for earthquake mitigation.
click here to see flow diagram for the maintenance of existing buildings
This maintenance process would include the continual upgrade of the following procedures as the need arises:
The development of these procedures should be flexible and fluid. Maintenance schedules for the building are required to ensure that building remains in an operable state and will continue to function in accordance with the design and operational management plan proposed.
These procedures should include the inspection in the case of a post-disaster function of:-
11.5 Disposal and Post Disaster
After an earthquake occurrence, inspections of all buildings, not just those for which the Queensland State Government has responsibility for, must be carried out, and each building must be classified as being "safe" "for occupancy" or "for operation", "is unsafe and requires repair " or is "unsafe and building requires demolition". This is normally carried out by experienced building inspectors or structural engineers specifically registered to carry out these inspections. One of the most important issues which must be included, is to ensure that all persons who occupied the building during the event have been accounted for. Injuries will be minimised if an emergency strategy is in place and all persons are aware of the emergency management plan and how it operates. Emergency service personnel may require immediate access to retrieve injured persons and this must be included in the plan. If the building has not been provided with post-earthquake safe operation, emergency service personnel may also be at risk while retrieving those injured.
As a consequence of an earthquake, the assessment of the building will include the requirements of emergency services for the:
- personnel - vehicles
Emergency Services organisations should be contacted to assist in the development of disaster strategies and plans for individual buildings.
click here to see flow diagram for post earthquake procedures
The risk of failure of a building can be assessed by allotting a level of potential vulnerability caused by:-
The level of potential vulnerability for a specific site can be comparatively assessed by a number of quite scientific methods, but a simple assessment can be achieved by adding the numerical value associated with the following performance criteria, and an example of this is:-
locality 1 soil profile 2 number of inhabitants 3 post-disaster function 3 Total 9
This valuation can then be used for comparison between various sites for suitability of the building type, use, post-disaster requirements and locality.
These performance criteria values, for a specific site and building type, are determined from the following comparative potential vulnerability factors:-
TABLE 12.1 SOIL PROFILE RISK
Soil Profile Comparative Risk Factor Type A 1 Type B 2 Type C 3 Type D 4 Type E 5
Refer Definitions for soil type
TABLE 12.2 LOCALITY RISK
Ground Acceleration Comparative Risk Factor 0.3 - 0.4 1 0.4 - 0.6 2 0.6 - 0.8 3 0.8 - 1.0 4 > 1.0 5
Refer AS1170 Part 4-1993 Earthquake Loads to determine the Ground Acceleration
TABLE 12.3 BUILDING RISK
Number of Comparative Risk Inhabitants Factor Less than 5 1 5 to 10 2 11 to 20 3 21 to 50 4 > 50 5
TABLE 12.4 POST DISASTER FUNCTION
Building Type Comparative Risk Factor Essential eg Hospital 5 Desirable eg Assembly 3 Hall Non Essential eg 1 Commercial Residential 1
Vulnerability could also inlcude the ability of services to minimise damage following an earthquake. Accordingly an additional classification could be added which reflects the number of essential services located within a building, eg. backup power, emergency water storge, fire systems, sewerage, communications equipment and computer systems.
TABLE 12.5 NO. OF SERVICES
13.0 COMPLIANCE WITH REGULATIONS
No. of Services Comparative Risk Factor 9 4 6 3 3 2 1 1
All buildings and structures are required to be designed in accordance with the following Australian Standards and the relevant standards pertinent to the building components being designed or constructed.
The following codes are both minimum and applicable to design for earthquakes in Australia to attain the potential for minimisation of failure due to earthquakes.
These Guidelines are to be used in the planning, design, management, operation and maintenance stages of a new building and shall also be used for the management and maintenance of existing buildings.
The Guidelines provide only a background to the requirements necessary for the planning, design management, operation and maintenance of any building or structure. Should any aspect not be covered in these Guidelines, advice should be sought from relevant professionals in engineering, architecture or building sciences with appropriate expertise and experience in earthquake engineering planning, design and emergency operation and management.
This Section of the Guidelines contains information that planners, designers and managers must consider during the relevant phases of the life of a building for earthquake damage mitigation and building management
Table 15.1 has been developed to assist those responsible to consider the relevant items during a particular phase of responsibility for the life of a building and indicates the clause of this Section relevant to a specific responsibility.
TABLE 15.1 - BUILDING COMPONENT - MANAGEMENT ASPECT IN EARTHQUAKE DAMAGE MITIGATION
PLANNING DESIGN ASSET MAINTENANCE POST-DISAS RISK
MANAGEMENT & TER
OPERATIONS DISPOSAL
SOIL 15.1.1 15.2.1 15.3.1 15.4.1 15.5.1 15.6.1
CONDITIONS
BUILDING 15.1.2 15.2.2 15.3.2 15.4.2 15.5.2 15.6.2
CLASSIFICATION
STRUCTURAL 15.1.3 15.2.3 15.3.3 15.4.3 15.5.3 15.6.3
MECHANICAL 15.1.4 15.2.4 15.3.4 15.4.4 15.5.4 15.6.4
ELECTRICAL 15.1.5 15.2.5 15.3.5 15.4.5 15.5.5 15.6.5
ARCHITECTURAL 15.1.6 15.2.6 15.3.6 15.4.6 15.5.6 15.6.6
HYDRAULIC 15.1.7 15.2.7 15.3.7 15.4.7 15.5.7 15.6.7
EXTERNAL 15.1.8 15.2.8 15.3.8 15.4.8 15.5.8 15.6.8
CONSTRAINTS
EMERGENCY 15.1.9 15.2.9 15.3.9 15.4.9 15.5.9 15.6.9
SERVICES
The basic matrix components components are defined horizontally by the building component factors and the columns by management aspects of the life cycle of the building. Each subsection references the management considerations of the building aspect requirements.
Other than the selection of the foundation system eg piles, bored piers, pad footings, strip footings or raft, the design of a building is significantly affected by the soil profile that exists at the particular site. Load coefficients are determined by the type of soil and the depth of the soil profile.
Each of the five (5) classifications of soil strata for general structures, vary the design loads imposed on a building and the type of structure required. The two(2) classifications for domestic structures provide basic coefficients for domestic design. These are all defined in the Australian Standard AS1170 Part 4 Earthquake Loads (See also Definitions).
15.0.2 Building Classification
The classification and purpose of the building also provides one of the design factors for determining the earthquake loads. Those buildings which form post-disaster functions such as hospitals and assembly buildings (which can house displaced persons), attract higher design load factors than those that do not.
There are also five (5) different levels of design methodology which are determined generally from the use of the building such as post-disaster functions, assembly of large crowds, or alternatively of limited numbers of people.
When considering a structural framing system to meet earthquake requirements, there are a number of issues that need to be addressed. These include:
There are also five (5) levels of design and detailing required in AS1170 Part 4, varying from simple static analysis and unreinforced masonry, to dynamic analysis and elimination of all masonry elements, towards completely reinforced masonry with specific detailing requirements for general buildings. For domestic structures, there are three (3) levels of design and detail requirements. Typical structural elements that must be considered are:
- timber - concrete - steel
- concrete - steel - timber
Selection of the appropriate foundation and framing system and attention to detailing requirements for masonry and framing are particularly important to in the minimisation of any potential earthquake damage.
Mechanical services are usually limited to major buildings such as assembly halls, hospitals, institutional, commercial and industrial buildings. The importance of these components is not only dependant upon their post-disaster function, but also on the possible effect on other components in the building such as pipework and electrical installations.
Consideration of the consequences of failure during planning and procurement, management and maintenance is critical to the post-disaster availability and functionality of the building.
Typical mechanical items in major buildings include:
Many of these items are fixed to the structure with vibration isolators for in-service operations, which in many cases are inadequate to resist earthquake loads, whereas pipework is often rigidly fixed to the adjacent support structure with no allowance for lateral movement between mechanical equipment and the structure.
Electrical services are provided generally to all buildings in varying capacities. The importance of continued operations after an earthquake is dependant upon the post-disaster requirements for the building.
It is highly probable that mains power will be discontinued due to faults and disconnections in supply lines after an earthquake. Hence the provision and successful operation of backup power is critical to the continued functionality of the building after an earthquake.
One could expect that after an earthquake, power generators could be in short supply. Hence the successful operation of the backup supply is critical.
Most failures and damage to buildings occurs due to loose items that slide off shelving, or falling from tall, slender, unsecured furniture. Other damage is caused by the brittle nature of unreinforced masonry walls. During earthquakes, loads are applied in all horizontal and vertical directions. Items that fail under these conditions are items that generally rely on gravity to remain in place. Ceiling tiles, light fittings and objects suspended from ceilings or roofs generally have little or no vertical or lateral support (especially for reversal of loads) or are inadequate to provide restraint during an earthquake. These objects can fall through opened grid systems and severely injure occupants below.
The building shape and framing system is critical to the successful resistance to an earthquake. Soft storeys should be avoided, eg. open undercover car parks within rigid framed buildings. Lift and stair shafts should be located symmetrically throughout the building. Otherwise the building will be subjected to torsional forces during an earthquake. Similarly heavy objects such as water storage tanks should be located within the centre of the building and as low as possible within the height of the building Heavy objects therefore should ideally be situated at ground level where swaying from the imposition of earthquake loads is reduced.
Water supply and sewerage systems are often damaged during an earthquake. Water pipes may rupture or shear depending on the severity of the earthquake and similar damage may occur to sewerage systems in the ground rendering those services inoperable after an earthquake.
These services are generally located underground and external to the building and rectification in the short term immediately after an earthquake is usually difficult to achieve due to access problems. Provision of these services after an earthquake would generally be of a temporary nature until full services can be provided which can take in some cases many months to reinstate.
15.0.8 External Site Considerations
Consideration of external services is particularly important for buildings having post-disaster functions such as hospitals. An earthquake depending on its severity, can shear off pipework for water, sewerage, gas and electricity. Fault lines or differential settlement of embankments after an earthquake may hinder emergency vehicles accessing emergency buildings or evacuating injured from non-emergency buildings.
During the planning stages of a building, planners should consider the following:-
Facilities such as hospitals, temporary accommodation for the displaced population and communications structures are critical to the Emergency Services organisations for quick response times and organisation of services.
Reliance on mobile telephones after an earthquake for emergency communications should not be made. If power is removed from the communications tower, or if the tower collapses then service in the area would be lost. Alternative methods of communication must be established.
Refer also to METHODOLOGY - DESIGN OF NEW BUILDINGS
- ASSESSMENT OF EXISTING BUILDINGS
- ASSESSMENT FOR VULNERABILITY
Planning for the design of all new buildings should incorporate a complete geotechnical investigation of the site to determine the effect of the soil profile on any earthquake imposed load. This will then allow a comparative assessment of alternative sites to be carried out. It will also highlight whether a building is located in a potentially high vulnerability area for earthquakes. The site investigation will also provide information to determine the type of construction required for the building and also the level of design required. It will also indicate to the building services engineers the standard of connections for services equipment required.
Most soil investigations for small projects may only go to a depth of 2 to 3 metres. In most domestic building cases this is sufficient as local geological conditions (where applicable) can be determined from local agencies.
For major building infrastructure projects such as hospitals, schools, commercial, institutional and industrial buildings, where the building can be used for post-disaster functions, soil profiles should extend to approximately 30 metres unless low or better strength rock is encountered. Care should be taken that the rock encountered is not a large boulder or seam.
The strength and depth of the soil has a bearing on the load factors, just as the locality of the site has a bearing on the load factors. These two load factors can significantly increase the strength requirements of the structure which will also affect project costs. Hence in order to minimise both costs (construction and life cycle maintenance) and vulnerability, the building should be located in a low risk area and on a good foundation strata.
All future developments should also be considered to ensure that the soil and foundation conditions do not change over the life of the building. For example, an increase in water table levels in sandy areas will increase the risk of liquefaction and or reduce the bearing capacity of the soil and accordingly may increase both the cost of construction and the building's vulnerability and reduce its life cycle availability.
15.1.2 Building Classification
The combination of the use and classification of the building and the soil conditions must be considered during planning for the location of the building as these two factors have cumulative load factors applied during the design of the structure, building components and building services. This will increase costs on the structure due to the increased loads to be resisted. Hence, the building especially with critical post-disaster functions, should be located in an area to minimise its vulnerability. This may be achieved for example, by locating the building on a site that has a soil profile comprising of dense gravelly material rather than loose sand or deep alluvial deposits.
In planning for the building's framing system, the type of minimum design and details required is controlled by the locality, soil conditions, and the use of the building. Reference should be made to Table 2.6 of AS1170 Part 4 which defines the type of design required for the appropriate soil conditions and type of building.
Selection of an appropriate locality and site with soil profile that minimises design loads provides significant savings to cost of the structure and framing requirements.
The earthquake design loads increase as the height above ground level increases. The load factor for this increase in height varies from 1 at ground level to 2 at the top of the structure. Hence during planning, the requirements for resistance against earthquakes is minimised by locating equipment at ground level. Location of equipment relative to other services and the consequences of failure must be considered.
For example, water storage tanks in high rise buildings are not designed to resist surge loads imposed on the side walls of the tanks by the movement of water during an earthquake. Hence the possibility of rupture of the tank is high. The forces from the earthquake induces imbalance loads from one side of the tank to the other. This can then cause a number of failures depending on the type of structure including;-
Electrical transformers, switch rooms, and lift motor rooms are often located in floors below these tanks. Rupture of the tank can then cause shorting of electrical equipment causing failure of main supply line electricity and backup power generation. This is of course assuming that the fuel supply lines for the generators have not sheared off due to differential movement or that electrical cables have not severed for the same reason. Other problems which can occur are the shearing off of vibration isolation brackets allowing equipment to move, causing supply or fuel lines to be broken.
As indicated in Section "15.1.4 Mechanical", components are subject to increased load factors as its location within a building increases in height. This is also true for electrical components. Hence, to minimise the stability requirements for electrical equipment they should be located in the lower sections of the building. This also assists in the maintenance of the equipment both on a (generally) daily basis and also after an emergency such as an earthquake.
Electrical components should be located away from, or protected from liquid conduits such as pipelines and drums which can burst, buckle and spill during an earthquake. If the electrical circuit shorts, the successful operation of backup systems can also be jeopardised.
Differential movements between fixed and moving items can cause wires to be pulled from fittings. It is therefore important that:-
Items that are located on shelves, if not anchored properly, can slide off or the shelf can collapse due to the imposed load. It is common during earthquakes for bottles, books etc. placed on shelves to slide off the end of shelves many metres away. Emergency supply battery packs are no different when stacked on shelves and these need to be supported both horizontally and vertically for constraint purposes.
In the planning stages, consideration needs to be given to all the vulnerable elements and whether these can be eliminated, reduced, or controlled.
The following items need to be considered to enhance the performance of a building during an earthquake:-
In the design of hydraulic services, allowances for movement between in-ground and above-ground fixtures shall be provided. Ensure that pipes are located away from electrical installations which may short-circuit if pipes rupture. Ensure pipes are fixed laterally and vertically in position. If pipes are free to move then movement joints in ends must be provided.
Check the capability of existing services such as water, power, sewerage and communication and the impact of failure on the building. Will these capacities be adequate for the builing requirements should an earthquake occur? Do existing services need to be upgraded to meet with the requirements? If the provision or upgrading of external facilities is not feasible, what emergency contingencies are in place to overcome any shortfalls in capacity should there be a possibility of failure.
Emergency services such as Police, Fire, Ambulance, Rescue Teams, Security Local Authorities and Agencies should be consulted to ensure that their needs are accommodated in the case of an earthquake eg.:
Has a list of equipment been made for use in disaster strategies? Ensure that records of the various Emergency Service providers in the building's area have up to date informatiion on the building and its occupants. Updates should be undertaken at intervals not exceeding six (6) months.
Refer also to METHODOLOGY - DESIGN OF NEW BUILDINGS
The soil that is encountered at a site can significantly increase the imposed earthquake loads on a building and its elements, and accordingly the type of foundations that are utilised, e.g. piled, piers, pad, strip or raft footings, etc.
The effect of the water table, type of soil and foundation must be considered, e.g. liquefaction of loose sands may occur on skin friction piles, and in this case, this type of pile would be inappropriate.
15.2.2 Building Classification
The classification of the building directly alters the factors used to determine the loads applied to the structure for design against structural failure due to earthquakes. Ensure that the design load factors that are used are applicable for the specific use of the building and for post-disaster functions if required and also to suit any future changes to the building's use, if it is known at the design stages.
Refer to METHODOLOGY - DESIGN OF NEW BUILDINGS
Minimum design and detail requirements apply to various types of structures according to their use and classification, locality and soil types.
The minimum design and structural framing requirements for various types of buildings are for example (from AS1170 Part 4):
Structure Type Typical Building Design Level
Description
III Hospitals C
II Assembly Hall B
I Not Residential and not II A
or III
Residential H1
Consideration to allow the transfer of loads is important in the design to resist and distribute earthquake loads and hence minimise damage. This transfer or load distribution would typically include the following:
Studies are being continually carried out to increase the data base of earthquakes to refine the soil and locality acceleration coefficients and updated inforrmation should be incorporated into all design aspects.
The applied load on mechanical equipment due to earthquakes increases as the location of the equipment in the building increases in height. Locating the equipment at the top of the building effectively doubles the applied load.
Good structural design as well as specifically located vibration isolators must be provided to resist these applied loads. Rigid fixings should also be designed to resist horizontal and vertical loads as friction forces are generally lost as the building vibrates.
Pipework attached to equipment should have provision for differential movement between the structure and the equipment. Vibration of equipment will occur in all directions.
Joints in pipework should be able to accommodate the expected rotations and lateral movements. Fixing of pipework at structural isolation joints should be spaced sufficiently apart to allow lateral movement between sections in all directions.
Refer also to Section 15.2.4 Mechanical as similar comments for mechanical equipment also apply to electrical equipment, and in addition;
Applied forces on equipment increases as the location in the building increases in height. The applied factor varies from 1 at ground level to 2 at the top of the building ie. applied loads are doubled.
During the design of a building to minimise earthquake damage the following aspects should be considered;
Reference should also be made to Section 15.2.4 "Mechanical" as hydraulic services provisions are similar. The following are typical of the items that need to be considered for earthquake damage mitigation:-
15.2.8 External Constraints - Refer to Section 15.0.8
15.2.9 Emergency Services - Refer to Section 15.0.9
See also METHODOLOGY - ASSET MANAGEMENT
- ASSESSMENT OF EXISTING BUILDINGS
During the life of a building, measures should be taken to ensure that conditions of the underlying soil strata remain unchanged or are improved. This is necessary to ensure that imposed earthquake loads do not increase, nor that the capacity of the soil to carry the load is not reduced. (eg. water table level change, saturated clays, etc.).
Planting of suitable and approved trees and shrubs can ensure that the water table remains constant or is reduced, is one way to maintain the properties of the soil, Care must be taken that the plants are not over watered which would be detrimental to the properties of the soil, and that the plants' root systems do not cauuse failure to the building's foundations.
The strategic management plan that is developed should include provision for the maintenance of the surrounding ground to ensure that the soil profile and soil properties are not altered from that existing prior to the construction of the building and used in the design of the building. This is particularly important when constructing in loose sands and silts where liquefaction can occur, potentially causing differential settlement of the building. It is equally important in other types of soil materials where the strength of the material is reduced, as this can cause slippage of embankments due to ground vibration.
15.3.2 Building Classification
During the life of a building, classifications can sometimes change or partially alter due to changes in use. A change in classification of the building or part of it may inflict a penalty on the asset management plan by increasing the design loads which the building must be able to resist in the case of an earthquake.
The asset manager should ensure that the strategic plan that is developed for the building includes the use of the building and its requirement for post-disaster functions (if required). If the building is designed for a domestic classification then it will not be able to upgrade to a higher (commercial, institutional) classification and still satisfy earthquake load resistance requirements. Property managers and designers should ensure that when a building changes classification or use, the building is able to meet the requirements of the Earthquake Loading Code AS1170 Part 4 as well as the Building Code of Australia requirements.
Ensure that any changes made to the building do not reduce the capacity of the existing structural system, and including:-
Equipment may be required for post-disaster functions and so equipment should be maintained in good working order to ensure that it will function in an emergency situation.
15.3.9 Emergency Services - Refer also Section 15.0.8 - Emergency Services
Refer also METHODOLOGY - MAINTENANCE OF EXISTING BUILDINGS
Ensure that all:-
Ensure that pipework integrity is maintained i.e.:
15.5 POST-DISASTER AND DISPOSAL
Refer also to METHODOLOGY - POST-DISASTER AND DISPOSAL
After an earthquake, the soil can become fractured or loose, considerably altering the capacity of the soil to support load. Aftershocks sometimes occur at different levels of magnitude after the main earthquake. These aftershocks can be up to the same magnitude as the original earthquake and be just as if not more drastic in effect, often due to the reduced capacity of the structure and the reduced capacity of the foundation material. This should be incorporated into a Post-Disaster Emergency Plan.
15.5.2 Building Classification
Refer also to METHODOLOGY - POST-DISASTER AND DISPOSAL
Refer also to METHODOLOGY - POST-DISASTER AND DISPOSAL
In the event of an earthquake, the following checks must be carried out:
Refer also to METHODOLOGY - POST-DISASTER AND DISPOSAL
In the event of an earthquake the following checks must be carried out:
Refer also to METHODOLOGY - POST-DISASTER AND DISPOSAL
In the event of an earthquake, the following checks must be carried out:
Refer also to METHODOLOGY - POST-DISASTER AND DISPOSAL
In the event of an earthquake, the following checks must be carried out:
Refer also to METHODOLOGY - POST-DISASTER AND DISPOSAL
In the event of an earthquake, the following checks must be carried out:
Rectification of external services could take some time and temporary services may be almost semi permanent. What contingencies are in place to accommodate this in the Management Plan?
15.5.9 Emergency Services - Refer Section 15.4.9
Refer also to METHODOLOGY and ASSESMENT OF VULNERABILITY
If the building has been designed in accordance with the appropriate codes and building requirements for earthquake mitigation, then the risk of failure due to an earthquake should be minimal. However if there are components in the building that fail or cause the building not to operate in the required manner e.g. loss of power, then the risk of failure can be considerable.
Soil conditions and their characteristics form one of the major risk components in earthquake design mitigation. The soil and foundations to the building, are one of the major factors which determine the design loads applied and the ability of the structure to resist the applied loads. This must always be assessed.
15.6.2 Building Classification
The building classification defines the use of the building which in turn defines some of the requirements on types of construction , limits on building sizes, fire compartments and occupancy levels for the purposes of fire resistance. It does not however define the type of construction required for earthquake resistance. hence the building classification alone cannot be used to attribute a level of vulnerability.
It could be assumed therefore, that if the occupancy level is low then the building would also have a low risk of failure, but this is not the case. In fact, it is the type of construction used in the "low risk" buildings that puts the occupants and the building in a high vulnerability category. For example, a 2 storey "six-pack" of domestic units which has a reasonably low level of occupancy, little post-disaster functionality, basement car park with masonry load bearing walls for support with little or no continuity from foundation level to roof has a very high risk (or is extremely vulnerable to failure) in the event of an earthquake.
Similarly, for example, a Class 10 building/structure (to BCA classification) which covers mast, flagpoles and antennas can be attributed different levels of risk. A flagpole, for instance, may have a minor post-disaster function whereas an antenna which is critical for radio communications between police, the public and emergency services would probably have a high post-disaster function. Consideration of this must always be taken into account when assessing RISK.
Hence those buildings which have the potential to contain a large number of people during an earthquake or have a post-disaster function have the highest potential risk associated with them, but must be designed to have the lowest potential risk.
The following typical risk levels have been determined by the number of people that could be injured or critically injured due to an earthquake in the event of failure.
CLASS DESCRIPTION RISK
1 Residential-single dwelling Low *
or townhouse
2 Residential-sole occupancy Low *
3 Residential-boarding house, Low */ Medium
hotel, aged care etc
4 Residential-a dwelling Low */ Medium
attached to a Class 5,6,7,8
or 9 building
5 Offices Medium
6 Retail (Shops) Medium
7 Car park/Wholesale Store Low
8 Processing Plant Medium
9 Health/Assembly High/Medium
10 Masts/Antenna Low/High
* These classes of buildings may have a low risk associated with them in terms of post-disaster functions but may be extremely vulnerable due to the general type of construction (unreinforced masonry).
15.6.3 Structural - Refer 15.6
Refer also 5.0 Typical Building Elements that are damaged during earthquakes.
15.6.4 Mechanical - Refer 15.6
Refer also 5.0 Typical Building Elements that are damaged during earthquakes.
15.6.5 Electrical - Refer 15.6
Refer also 5.0 Typical Building Elements that are damaged during earthquakes.
15.6.6 Architectural - Refer 15.6
Refer also 5.0 Typical Building Elements that are damaged during earthquakes.
15.6.7 Hydraulic - Refer 15.6
.
Refer also 5.0 Typical Building Elements that are damaged during earthquakes.
15.6.8 External Constraints - Refer 15.6
Refer also 5.0 Typical Building Elements that are damaged during earthquakes.
15.6.9 Emergency Services - Refer 15.6
Refer also 5.0 Typical Building Elements that are damaged during earthquakes.
These guidelines outline the methods of repairing buildings after an event. It includes the determination of loads, soil condition criteria, hazard levels, framing systems and models and analysis of the various building systems.
This document contains a number of sketches and photographs which identify the various building types and framing systems as well as identifying the potential hazard components of a building and the failure mechanisms.
Contains a number of typical forms used for evaluating seismic resistance of buildings including the responses.
This document outlines a number of procedures for rapid visual screening of buildings for potential hazard and has developed a series of question and answer checklists to assist in the screening.
This book contains a variety of studies and photographs which indicate typical damage areas and indicates where damage can occur and where to look for it in areas which failure is not always visible from the outside.
Identifies a number of different framing systems and contains procedures forms for evaluation of existing buildings.
The Swiss Reinsurance Company report on damage caused by the Newcastle earthquake.
A report prepared by the Munich Reinsurance Company on the effects, causes and implications of the Newcastle earthquakes and outlines costs to the insurance industry.
Document prepared by the Institution of Engineers, Australia discusses issues such as construction, design, insurance, previous seismicity, safety assessment, post disaster functions, risk management and heritage issues that were raised due to the Newcastle Earthquake.
Reports by the various emergency departments into the procedures undertaken after the event and the problems that occurred.
A series of papers and notes on the Newcastle Earthquake ranging from design issues, emergency procedures, insurance aspects, construction issues, latent defects.
This document specifies minimum earthquake design load on buildings and components.
This document specifies the minimum combinations of loads on buildings.
An outline of the different methods used by the various countries in the earthquake hazard assessment for their areas.
Specifies the procedures to be undertaken for the demolition of some of the various types of structures.
Report which outlines the development of the earthquake zonation in Australia, in particular South East Queensland.
A discussion on the limitations of the typical method of determining earthquake risk as used by other countries for Australia.
Paper discussion on the method of determining the earthquake zones in Australia, in particular Sydney.
A paper discussion on the Implications of Continental Earthquakes, (Intraplate no tectonic) on engineering design, construction and insurance.
Paper discussion on the geology, history of the area, seismicity, extent of damage and design requirement in the Newcastle area after the Newcastle Earthquake.
University of Queensland http://shakes.earthsciences.uq.edu.au/
Harvard http://tempo.harvard.edu/homepage.html
Applied Technology Council http://www.atcouncil.org
Washington http://www.geophys.washington.edu/seismosurfing.html
Carleton http://www/cieng/carleton.ca/cqi-bin/quakes